Optional Calculations for Computing Feeder and Service Loads 220-30.
Optional Calculation – New Dwelling Unit
Feeder and Service Load. For a dwelling unit having the total connected load served by a single 3-wire, 120/240-volt or 208Y/120-volt set of service-entrance or feeder conductors with an ampacity of 100 or greater, it shall be permissible to compute the feeder and service loads in accordance with this section instead of the method specified in Part B of this article. The calculated load shall be the result of adding the loads from (b) and (c). Feeder and service-entrance conductors whose demand load is determined by this optional calculation shall be permitted to have the neutral load determined by Section 220-22.
General Loads. The general calculated load shall be not less than 100 percent of the first 10 kVA plus 40 percent of the remainder of the following loads:
Heating and Air-Conditioning Load. Include the largest of the following six selections (load in kVA).
Optional Calculation for Additional Loads in Existing Dwelling Unit
For an existing dwelling unit presently being served by an existing 120/240-volt or 208Y/120-volt, 3-wire service, it shall be permissible to compute load calculations as follows:
Load (kVa) Percent of Load
First 8 kVA of load at 100
Remainder of load at 40
Load calculations shall include lighting at 3 volt-amperes/ft2 (0.093 m2); 1500 volt-amperes for each 2-wire, small-appliance branch circuit and each laundry branch circuit as specified in Section 220-16; range or wall-mounted oven and counter-mounted cooking unit; and other appliances that are permanently connected or fastened in place, at nameplate rating.
If air-conditioning equipment or electric space-heating equipment is to be installed, the following formula shall be applied to determine if the existing service is of sufficient size.
| Air-conditioning equipment*.................. | 100% |
| Central electric space heating*............. | 100% |
| Less than four seperately controlled space-heating units*.............................. | 100% |
| First 8 kVA of all other loads.................. | 100% |
| Remainder of all other loads................. | 40% |
*Use larger connected load of air conditioning and space heating, but not both.
Other loads shall include the following: