PRODUCT SPECIFICATIONS TABLE
COMMERCIAL 208 VOLT (AC) OPERATION, 240 VAC RATING
<< back to the
Product Guide
Commercial and industrial locations are often
served by 208 V three-phase electrical services. Where 240-V rated tankless
water heaters are used at 208 V, their available wattage, and therefore
their temperature rise, are de-rated by 25%. The table below shows which
ratings are affected. Other specifications are the same as for 240 V
operation.
FOUR CHAMBER MODELS
|
MODEL |
RA-28 |
RA-22 |
RA-18 |
|
kW |
21 |
16.5 |
13.5 |
|
Elements |
7000 watts
' 4 |
5500 watts
' 4 |
4500 watts
' 4 |
|
BTU/hour |
71670 |
56310 |
46070 |
|
kg-cal/min. |
300 |
236 |
194 |
|
Temperature Rise |
71 °F @ 2.0 GPM
57 °F @ 2.5 GPM
48 °F @ 3.0 GPM
36 °F @ 4.0 GPM
37 °C @ 8 L/min
30 °C @ 10 L/min
25 °C @ 12 L/min
19 °C @ 16 L/min |
56 °F @ 2.0 GPM
45 °F @ 2.5 GPM
37 °F @ 3.0 GPM
28 °F @ 4.0 GPM
30 °C @ 8 L/min
24 °C @ 10 L/min
20 °C @ 12 L/min
15 °C @ 16 L/min |
45 °F @ 2.0 GPM
36 °F @ 2.5 GPM
30 °F @ 3.0 GPM
22 °F @ 4.0 GPM
24 °C @ 8 L/min
19 °C @ 10 L/min
15 °C @ 12 L/min
12 °C @ 16 L/min |
|
ELECTRICAL |
|
V |
208 |
208 |
208 |
|
A (max) |
101 |
79 |
65 |
|
Hz |
50 / 60 |
50 / 60 |
50 / 60 |
|
Circuits |
30A x 4 |
50A x 2 |
40A x 2 |
back to top |
|